DESCRIPTION
ADCA sample coolers are specially designed to cool samples of boiler water or steam for analysis. Sample coolers prevent steam flashing-off from hot pressurised liquid samples, which can be dangerous and will result in an incorrect water sample. This device may be used for boiler water analysis and other sampling or cooling applications compatible with construction materials.
MAIN FEATURES
Corrosion-resistant body and internals. Self draining sample (inlet top, outlet bottom).
OPTIONS:
- Sample inlet valve.
- Cooling water inlet valve.
- Temperature indicator
- Bolted top plate.
- Different connection sizes and materials under request.
- Double coil high pressure design for larger capacities
USE:
Steam boilers and hot water systems.
AVAILABLE MODELS:
SC32/SS – SC132/SS – stainless steel body and coil.
SIZES AND CONNECTIONS :
SC32 – SC132
Cooling water inlet/outlet : 1/2” on body (BSP or NPT)
Sample tube inlet/outlet : 8 mm O/D
INSTALLATION:
Vertical installation.
OPERATION:
Cooling water must be in its maximum flow before open or close the sample inlet valve, in order to avoid the risk of scalding. The sample valve must also be closed before the cooling water valve.
PERFORMANCE:
30 to 60 kg/hr of sample water at ≈ 30oC with 1m3/h -15oC inlet cooling water (boilers up to 20 bar-220oC), for other pressures, temperatures and /or certified figures please consult.